
Figure 1. Earthing Transformer
An earthing transformer, also known as a grounding transformer, is a special type of transformer used in electrical power systems to provide a neutral point and a safe path for ground-fault current in networks that lack a natural neutral, such as delta-connected systems. Its primary function is to create a synthetic neutral so that protective devices can detect and clear line-to-ground faults, preventing dangerous overvoltages and maintaining stable phase voltages during unbalanced conditions. Earthing transformers are used in distribution networks, industrial plants, and renewable energy installations where grounding is required for system protection and reliability. By supplying the required zero-sequence current during a fault, they improve overall system safety, stability, and fault-clearing capability.
An transformer is typically constructed using either a zigzag (Zn) winding configuration or a delta–wye (Δ–Y) transformer arrangement, both designed to create a neutral point and allow zero-sequence current to flow during ground faults. The most popular construction is the zigzag connection, where each phase winding is split into two equal coils wound on different legs of the core and interconnected in such a way that normal phase currents cancel out while zero-sequence currents combine effectively. This gives the transformer low impedance to ground-fault currents but high impedance to balanced three-phase currents, making it efficient and stable in normal operation.
The transformer is typically built on a laminated steel core with robust insulation designed to handle fault currents for short durations. Many earthing transformers include a resistor or reactor connected between the neutral point and ground to control and limit fault current to safe levels. Depending on system requirements, the unit may be oil-immersed or dry-type, equipped with cooling arrangements (such as ONAN), protective relays, and grounding terminals.
An earthing transformer works by creating a neutral point in power systems that do not naturally have one and by providing a controlled path for zero-sequence (ground-fault) current. Under normal operating conditions, the transformer carries little to no current because the balanced three-phase currents cancel out within its special winding arrangement, most commonly the zigzag connection.
However, when a line-to-ground fault occurs on the system, the balance is disturbed, and zero-sequence current flows through the earthing transformer. The transformer then supplies this current from its artificially created neutral, allowing protective relays to detect the fault and isolate the affected part of the system. If a neutral grounding resistor (NGR) or reactor is installed, it limits the magnitude of the fault current to a safe level. Earthing transformer remains nearly inactive during normal operation but becomes essential during ground faults, ensuring system stability, proper grounding, and reliable fault clearing.
To see how an earthing transformer provides a stable grounding path, we need to look at its most common winding setup, the zigzag connection.
A zigzag connection is a widely preferred winding arrangement for earthing transformers because it is designed to create a stable neutral point and allow ground-fault current to flow when needed. In a zigzag transformer, each phase winding is split into two equal parts, and these coil halves are wound on different legs of the core in opposite directions. This special arrangement causes the normal three-phase currents to cancel out within the windings, meaning the transformer carries almost no current during regular operation. However, when a line-to-ground fault occurs, the unbalanced (zero-sequence) current does not cancel out. Instead, it combines in the zigzag windings and flows to the neutral point created by the transformer, providing a safe path for fault current.

Figure 2. Distribution of Ground-Fault Current in the Zigzag Winding
Because of this unique behavior, blocking balanced currents while allowing zero-sequence currents, the zigzag connection provides a stable neutral, helps maintain proper voltage balance, and supports reliable fault detection and fault clearing in systems that would otherwise remain ungrounded.
Each Earthing transformers type designed to provide a neutral point and manage ground-fault currents in systems that lack a natural neutral. The main variations depend on how the transformer windings are arranged and how the grounding connection is achieved. The two primary types are:

Figure 3. Earthing Transformer Types
This type features a zigzag winding pattern where each phase is split and wound on different legs of the core. It offers low impedance to zero-sequence current and remains nearly inactive during normal operation. Zigzag transformers are favored for their efficiency, compact design, and strong performance during ground-fault conditions.
This configuration uses a delta-connected primary and a grounded wye secondary. The grounded wye winding provides the neutral point needed for the system. Although slightly larger than zigzag designs, delta–wye transformers can also supply auxiliary power if required, making them suitable for certain industrial applications.
During a ground fault, an earthing transformer becomes active and provides the path needed for zero-sequence current to return to the system neutral. Under normal conditions, the transformer carries little or no current because the three-phase currents are balanced and cancel each other within its windings. When a line-to-ground fault occurs, this balance is disturbed, and an unbalanced current is created. The earthing transformer allows this current to flow through its windings and into the neutral point it provides, giving protective devices a clear indication that a fault is present.
Depending on the system design, a neutral grounding resistor (NGR) or reactor may be connected between the transformer’s neutral and ground to control the fault-current level and prevent excessive damage. By safely channeling zero-sequence current and stabilizing phase voltages during the fault, the earthing transformer helps ensure quick fault detection, proper isolation of the affected section, and overall system stability.
When an earth fault happens outside the protection zone of a star-delta transformer, some fault current can circulate within the CT loops without reaching the differential relay. Because this circulating current does not flow through the relay’s operating coils, the protection system stays stable and does not trip incorrectly.
A zigzag earthing transformer helps keep the system stable because its winding design cancels out magnetic flux when zero-sequence current flows. During an external earth fault, the fault current splits equally in the zigzag windings, and the flux cancels, allowing the current to pass with low impedance.
This cancellation prevents false imbalance signals and ensures the protection system only reacts to real internal faults. As a result, the system remains secure, and the earthing transformer safely provides the return path required during external earth faults.
System Voltage Rating - earthing transformer must match the line-to-line voltage of the system it is connected to. This ensures proper insulation, safe operation, and compatibility with other equipment.
Neutral Voltage Rating - neutral point created by the transformer must withstand temporary overvoltages that occur during ground faults. This rating ensures the neutral remains stable and does not experience insulation stress.
Fault Current Rating - transformer is rated to handle a specific level of ground-fault current for a short duration, typically 1-10 seconds. This rating depends on the system’s grounding method and protection coordination.
Continuous Current Rating - Although earthing transformers normally carry little to no current during normal operation, a small continuous current rating is provided to account for system unbalance and minor zero-sequence currents.
Impedance Rating - transformer’s zero-sequence impedance determines how much ground-fault current will flow. Lower impedance allows higher fault current, while higher impedance limits it. This value is essential for relay coordination and system protection.
Thermal Rating - transformer must withstand the heat generated during high fault-current flow. Its thermal rating is designed to prevent insulation damage and maintain safe operation under short-duration faults.
• Match the system voltage - transformer must be built for the same voltage level as the power system it connects to.
• Ground-fault current limit - Its design should control how much current can flow during a ground fault. This depends on the transformer’s impedance and whether a resistor or reactor is added.
• Fault current rating - transformer must be strong enough to handle high fault current for a short time, usually a few seconds.
• Continuous current rating - even though it normally carries very little current, it should support small unbalanced or neutral currents safely.
• Cooling and heat handling - transformer must be able to handle the heat produced during faults, whether it is air-cooled or oil-cooled.
• Winding arrangement - the zigzag or delta-wye winding setup should be chosen based on the system’s grounding needs.
• Installation needs - the design should consider space, mounting, and environmental conditions where the transformer will be placed.
• Safety and protection features - devices like temperature sensors or protective relays may be included to keep the transformer safe during abnormal conditions.
Delta-Connected Power Systems - Earthing transformers are installed in delta systems to create a neutral point, since these systems do not naturally have one.
Industrial Plants - Large factories usually use them to provide proper grounding for equipment and to ensure safe operation during ground faults.
Renewable Energy Systems - Wind farms, solar farms, and other renewable installations use earthing transformers to stabilize the system and support fault protection.
Generator and Transformer Banks Without a Neutral - When multiple generators or transformers are connected in delta or isolated arrangements, an earthing transformer supplies the needed neutral point.
Medium-Voltage Distribution Networks - Utilities use earthing transformers in distribution lines to improve grounding, support protective relays, and reduce overvoltages.
Ground-Fault Detection and Protection - They provide the return path required for relays to detect line-to-ground faults and trip the breakers safely.
Systems Requiring Controlled Fault Current - When paired with grounding resistors or reactors, earthing transformers help limit fault current to prevent equipment damage.
Advantages of Earthing Transformers:
• Provides a neutral point in systems that do not have one, such as delta-connected networks.
• Improves system safety by giving ground-fault current a proper path.
• Helps protective relays operate correctly during ground faults.
• Reduces over-voltages caused by unbalanced or fault conditions.
• Supports stable voltage levels across the system.
• Can limit fault current when used with grounding resistors or reactors.
• Perfect in renewable and industrial systems where grounding is essential.
Disadvantages of Earthing Transformers:
• Adds extra cost to the power system installation.
• Requires space and installation arrangements, especially for large units.
• Can experience heating during high fault currents, needing proper cooling.
• Needs regular inspection and maintenance to ensure reliable operation.
• May introduce additional losses, even though they are usually small.
• Incorrect sizing or design can lead to insufficient grounding or protection issues.
Earthing transformers are important for keeping electrical systems safe and stable. They provide a neutral point, help detect ground faults, and protect equipment from damage. With the right design and installation, they help power systems work safely and reliably.
ABOUT US
Customer satisfaction every time. Mutual trust and common interests.
Transformer Core Basics: Parts, Function, and Designs
2025-11-25
Dry-Type Transformers: Clean, Safe, and Reliable Power
2025-11-25
They need one because isolated or delta-connected systems do not have a natural neutral point, and the transformer provides a safe ground connection.
Ground faults may not be detected, voltage may increase dangerously, and equipment may be damaged.
Are not.The grounding transformer creates the neutral point, while the resistor limits the fault current through that neutral point.
Usually from 1 to 10 seconds, depending on its design and heat level.
Ground fault relay, overcurrent relay, temperature sensor and ground fault indicator.
Email: Info@ariat-tech.comHK TEL: +852 30501966ADD: Rm 2703 27F Ho King Comm Center 2-16,
Fa Yuen St MongKok Kowloon, Hong Kong.